|
Home USFA AFCI Fact Sheet contact
| |
....................
Arc-fault circuit Breaker
An arc fault circuit breaker or interrupter (arc
fault circuit breakers) is a circuit breaker
designed to stop fires by sensing non-functional
electrical arcs and disconnect power before the arc
starts a fire. The arc fault circuit breakers should
distinguish between a working arc that may occur in
the brushes of a vacuum sweeper, light switch, or
other household devices and a non-working arc that
can occur, for instance, in a lamp cord that has a
broken conductor in the cord from overuse. Arc
faults in a home is one of the leading causes for
household fires.
Arc fault circuit breakers look like a GFCI/ circuit
breaker (Ground-Fault Circuit Interrupter in that
they both have a test button, although it is important
to distinguish the difference between the two. GFCIs are designed
to protect people against electrical shock, while arc fault
circuit breakers are primarily designed to protect
against fire.
Electrical Code Requirements
Starting with the 1999 version of the National
Electrical Code in the United States and the 2002
version of the Canadian Electrical Code in Canada,
arc fault circuit breakers are now required in all
circuits that feed receptacles in bedrooms of
dwelling units. The National Electrical Code is an
industry consensus document adopted by many U.S.
municipalities. This requirement of the NEC is
typically accomplished by using a kind of
circuit-breaker (defined by UL 1699) in the breaker
panel that provides combined arc-fault,
ground-fault, and over-current protection.
The arc fault circuit breakers is intended to
prevent fire from arcs to ground and works at a
higher threshold (30 mA) than the GFCI/RCD
(Ground-Fault Circuit Interrupt/Residual-Current
Device) implementations protecting against the
safety hazard of electric shock (which operate at 6
mA). However, advanced electronics inside an arc
fault circuit breakers breaker detect sudden bursts
of electrical current in milliseconds, long before
they would trip a regular overcurrent circuit
breaker or fuse. Combined devices are available
which trip at the lower, 6 mA threshold of a true
GFCI/RCD.
In 2002, the NEC removed the word "receptacle"
leaving "outlets", in effect adding lights within
dwelling bedrooms to the requirement [debated
interpretation]. The 2005 code made it more clear
that all outlets must be protected, despite code
making panel discussion about excluding bedroom
smoke detectors from the requirement.
Beginning Jan 2008, only "combination type" arc
fault circuit breakers' will meet the NEC
requirement. These can protect cords as well as
wiring.
Limitations
Even arc fault circuit breakers, however, do not
provide protection against all of the possible
circuit faults that could ignite a fire. In
particular, they provide no special protection
against so-called "glow faults" where a relatively
low-resistance short circuit draws a modest amount
of current (within the trip limits of the circuit
breaker) but heats the localized area of the fault
to red heat. Glow faults also can occur where a
connection in series with a load suddenly develops a
high resistance; this might be the result of a
now-defective switch, socket, plug, or wire
connection (series faults are also commonly observed
in aluminum wire junctions). No practical circuit
breaker could detect either such fault as there is
no measurable characteristic that any circuit
breaker could employ to distinguish a glow fault
from the normal operation of a branch circuit.
|
|
|
|